Choosing between a single-phase and a three-phase construction site distribution box depends on the equipment you need to power. Single-phase (230 V) suits portable power tools, such as a drill or a breaker. Three-phase (400 V) is for powerful machines, such as cranes or concrete mixers, according to the 123elec selection guide (in French). Beyond voltage, you need to check the number of sockets, the protective devices, the IP and IK ratings and compliance with construction site standards.

This article details these criteria and explains what a glass fibre reinforced polyester enclosure changes on a construction site.

Single-phase or three-phase: what is the difference on site?

A site distribution box provides the temporary power supply for a construction site. It distributes power across several sockets, each one protected.

The single-phase distribution box (230 V)

In single-phase, the voltage is 230 V. 16 A sockets with two poles and earth (2P+E) power portable tools, lighting and small equipment. In the United Kingdom, portable tools on site are usually supplied at 110 V through a transformer, as recommended by BS 7375.

The three-phase distribution box (400 V)

In three-phase, the voltage is 400 V. IEC 60309 industrial sockets 3P+N+E (three phases, neutral and earth), rated 16 A or 32 A, power high-output machines, such as cranes or concrete mixers.

Many three-phase boxes combine both: several 230 V sockets and one 400 V socket in the same unit. A three-phase box can therefore serve both types of equipment.

How to size your requirements

The safest method is to list the equipment, note its voltage and power, then check that the total of the devices used at the same time is compatible with the rating of the box and of the supply connection.

Distribution, floor, trade: the three families of site boxes

On a construction site, the temporary supply is often organised on three levels, which can also be found in the Legrand catalogue of site distribution boxes (in French).

The distribution box

It is transportable. It supplies the floor boxes and various site equipment, with outlets from 16 A to 63 A on a catalogue model.

The floor box

It provides the temporary supply for the electrical equipment of all trades in the building, particularly finishing works, according to the P17 box datasheet. A built in handle makes it mobile.

The trade box

It is also mobile. It directly supplies one worker’s portable power tools.

Choosing a box therefore starts with knowing where it sits in this chain: main distribution, floor or workstation. Each level has a different rating, different sockets and different mobility constraints.

Criteria for choosing a construction site distribution box

Sockets, power and protective devices

  1. Number and type of sockets. 230 V 16 A sockets for everyday tools, 400 V 16 A or 32 A sockets for machines. Allow a few spare sockets for needs that change as the work progresses.
  2. Maximum power. It must cover the equipment used at the same time.
  3. Protective devices. 30 mA residual current protection (RCD), circuit breakers rated for the sockets, emergency stop and voltage indicator, as detailed in the P17 box datasheet. The RCD protects against indirect contact, the circuit breaker protects the circuits against overload: both are needed.

Mobility, IP and IK ratings

  1. Mobility. Handle, weight, wall or stand mounting, ability to coil the cable for transport.
  2. IP and IK ratings. The IP rating (IEC 60529) measures protection against dust and water, the IK rating (IEC 62262) impact resistance. On an equipped box, the rating also depends on the sockets and covers, not only on the enclosure. The levels are detailed on the IP/IK protection rating page.

Compliance and standards

Site distribution boxes fall under the IEC 61439 part 4 standard (BS EN 61439-4), dedicated to assemblies for construction sites: transportable or mobile assemblies, used indoors and outdoors, up to 1,000 V AC. Installation follows IEC 60364-7-704 on construction and demolition sites, which corresponds to section 704 of BS 7671 in the United Kingdom.

National health and safety rules for construction sites also apply, such as the Construction (Design and Management) Regulations 2015 in the United Kingdom. This framework should be checked case by case for each site.

Read the datasheet before choosing

A site distribution box datasheet reads like a checklist. For example, the datasheet of a floor box on the market specifies:

  1. the materials of the enclosure and the window;
  2. the IK and IP ratings, the latter given for the box fitted with sockets and cable;
  3. the operating temperature, from minus 25 °C to plus 40 °C on this model;
  4. the glow wire resistance of the enclosure, 650 °C for 30 seconds on this model;
  5. UV resistance, tested for 168 hours on this model;
  6. the fault current withstand, 10 kA on this model;
  7. the minimum supply cable cross section according to current: 2.5 mm² for a 16 A box, 6 mm² for 32 A, 10 mm² for 40 A.

These values are specific to this model. The point is to compare enclosures on the same lines, including a polyester box, whose datasheet should give the same information.

Why a polyester enclosure on a construction site

A construction site exposes the enclosure to rain, dust, impacts and repeated handling. Glass fibre reinforced polyester meets these demands on several points.

Corrosion, insulation and finish

  1. It does not rust. Its corrosion resistance limits maintenance and repainting.
  2. It is insulating. The enclosure does not conduct electricity.
  3. Its surface can be treated. On Europoly cabinets, a gel coat surface layer improves resistance to chemical and weather attack.

Heat, cold and condensation

Temperature variations and hot and cold cycles accelerate fatigue in joints and ageing of seals. In the sun, a closed enclosure can heat up. Condensation forms when the walls or internal components are colder than the dew point of the air inside. Since the IP rating does not cover moisture generated by condensation, a thermally poorly designed enclosure can suffer corrosion and insulation faults, even with a high rating. The balance between sealing and ventilation is covered in the article polyester enclosure: ventilation or weatherproofing.

UV resistance

For polymer and composite materials, UV exposure is an ageing factor. It is checked through accelerated ageing tests, such as those in the ISO 4892 series, which combine light, humidity and wetting cycles, as Europoly explains.

Performance figures (permissible temperatures, mechanical loads) are given on the product datasheet of the chosen model. To compare enclosures and cabinets, see the page polyester electrical enclosures for industry.

The models are presented on the polyester construction site boxes product page.

From box to complete project: Europoly, Polyelec and Gensollen

A site distribution box is part of an installation that needs wiring and sometimes housing. The three companies of the group cover these steps.

Europoly, the polyester enclosure

Europoly manufactures enclosures, cabinets and cabins in glass fibre reinforced polyester.

Polyelec, wiring and electrical integration

On request, Polyelec carries out the internal wiring and electrical integration of the group’s enclosures.

Gensollen, cabins and fit out

Gensollen offers complete fit outs for polyester cabins and cabinets: fixed and sliding furniture, HVAC ventilation, raised floors for cable routing. This offer meets needs that go beyond a simple box.

Installation and proper use

Installing and connecting

Connection and installation must be carried out by a qualified electrician, in line with IEC 60364-7-704 (BS 7671 section 704 in the United Kingdom).

  1. Place the box on a stable surface or fix it to a suitable support.
  2. Supply the box with a cable whose cross section matches the box current rating.
  3. Plug each piece of equipment into the socket of the correct voltage: 230 V or 400 V.
  4. Do not exceed the box rating. In case of overload, unplug the devices and check the connections before switching back on.
  5. Regularly check the condition of the enclosure, cables and protective devices.

Common mistakes to avoid

  1. Thinking the RCD is enough. A residual current device does not protect against overload. According to the datasheet of a box on the market, you need to check that both protection against indirect contact and protection against overload are provided.
  2. Undersizing the supply cable. The minimum cross section depends on the box current rating: a cable that is too thin heats up and trips the protective devices.
  3. Plugging equipment into the wrong voltage. A 230 V socket does not replace a 400 V socket, and vice versa.

Frequently asked questions

What is the difference between a single-phase and a three-phase site distribution box?

Single-phase supplies 230 V, suited to portable power tools. Three-phase supplies 400 V, suited to powerful machines such as cranes or concrete mixers.

When should you choose a three-phase site distribution box?

When the site has high-power machines to supply at 400 V. Many three-phase boxes also include 230 V sockets for everyday tools.

Which tools can be plugged into a single-phase site distribution box?

Portable power tools, such as a drill or a breaker, as well as lighting and small 230 V equipment.

Which standards apply to a construction site distribution box?

The IEC 61439 part 4 standard (BS EN 61439-4) sets the requirements for construction site assemblies. Installation follows IEC 60364-7-704, section 704 of BS 7671 in the United Kingdom. IP and IK ratings are defined by IEC 60529 and IEC 62262.

Why choose a polyester enclosure for a site distribution box?

Glass fibre reinforced polyester does not rust, resists corrosion and does not conduct electricity. This limits maintenance on an enclosure exposed to rain, dust and impacts.